1-10 BUS MOTION SENSOR |
Model | SUO110A |
---|---|
Voltage range | 220V - 240V |
Integrated ambient light sensor | Yes |
Angle | 360º |
Maximum detection diameter | 16m |
Maximum installation height | 8m | Maximum controllable power | 500mA bus 1-10 | Size | 92X52X25mm |
Detection area | 10, 25, 50, 75, 100% |
Running time after detection | 10s, 30s, 90s, 3m, 20m, 30m |
% power at rest | 50, 40, 30, 20, 10% |
Outside light | 5Lux, 10Lux, 30Lux, 50Lux o deactivate |
Control bus | 1-10V |
Advance sensor with 1-10 bus integrated control. It allows to dim the output depending on the situation.
After any movement is detected, load is set to 100% (if lights sensor allows it) after delay time, light goes down smoothly 0%, 10%, 20%, 30%, 40% o 50% depending on desired/set (2 step). If it es required it is possible to set a new timer to turn completely off the light/load after that time (3 step).
This item is specially recommended to save energy when there is no people in the room but without leaving the space completely dark. |
|
![]() ![]() ![]() |
|
Without detection, lamp power remains with the minimum selected all the time.
The sensor turns on the lamp when motion is detected.
When the set time passes, the lamp gradually becomes minimal set if no detection. |
|
|
![]() ![]() ![]() |
|
In low ambient light sensor automatically turns the lamp when motion is detected.
After the waiting time, the sensor attenuates the lamp to a low light level if no new activation motion.
After the rest period, the sensor lamp off after no motion is detected in the detection zone. |
|
|
|
![]() ![]() ![]() |
|
If the ambient light is sufficient, the lamp remains off.
With sufficient ambient light detection if the lamp will not light.
If the ambient light is insufficient but detection, the lamp will turn on. |
Detection area |
|
![]() |
Detection area is set by combining the switches. |
% Resting power |
|
![]() |
Stand by light level you want after delay time. |
Running time after detection. |
|
![]() |
Peroid of time the lamp remains at 100% light after last movement. |
Time out |
|
![]() |
Peroid of time the lamp is kept at a low level of light, before shutting undetected. When set to off mode low light intensity is maintained until motion is detected. |
External light |
|
![]() |
Minimum external light so that the sensor is activated. in the off mode. the sensor turns on when motion is detected regardless of the ambient light level. |
25W LED Downlight |
LED Panel |
![]() |
![]() |
PWD253NR - PWD254NR |
P6P40X4 - P6P40X6 - Superficie / Continuo P3P40X4 - P3P40X6 - Superficie / Continuo P12P7X4 - P12P7X6 - Superficie / Continuo |
LED high bay |
Modular LED high bay |
![]() |
![]() |
PHC1206NR - PHC1456NR - PHC2006NR |
PHCK07R - PHCK14R - PHCK21R |
Neophos fitting |
Weather proof fitting |
![]() |
![]() |
LPL0620NR - LPL1240NR | LPL06236R - LPL12236R - LPL12258R |